Characteristics

Construction
  • 1 PCB-Main Electronic board
  • 2 SMART-MT controller
  • 3 PCB-Main display
  • 4 PCB-Terminal Block System
  • 5 Air vent valve
  • 6 Safety valve
  • 7 Supply terminal block
  • 8 Heat exchanger (water)
  • 9 DC-Inverter compressor
  • 10 Water discharge valve
  • 11 Circulation pump
  • 12 Sensor of external air temperature
  • 13 Heat exchanger (air)
  • 14 Water flow connection to the system
  • 15 Serial number
  • 16 Base heater
  • 17 Water return connection from the system

Constructional characteristics
• DC-Inverter hermetically sealed compressor and thermal protection.
• Electronic expansion valve.
• Water side plate exchanger.
• Air side exchanger with aluminium flaps and copper pipes.
• Propeller type fan with brushless DC motor and accident-prevention protective grid.
• Innovative SMART-MT regulator.
• PCB-Terminal Block electronic board.
• Painted steel structure.

Working range
Maximum outdoor temperature: 43 °C (Cooling), 43 °C (Heating)
Maximum water temperature: 23 °C (Cooling), 60 °C (Heating)
Minimum outdoor temperature: 18 °C (Cooling), -20 °C (Heating)
Minimum water temperature: 6 °C (Cooling), 23 °C (Heating)
CodeModelDimensions WxHxD mmCapacity kW (Heat)*Capacity kW (Cool)**COP*/EER**
07247911EH0615DC898x675x3156,85 (2,07 - 6,85)5,30 (0,92 - 5,30)4,25 / 3,85
07247931EH1015DC871x882x3559,98 (2,64 - 11,2)9,00 (2,97 - 9,00)4,50 / 3,66
07247941EH1315DC1024x1418x35613,5 (8,00 - 13,5)14,3 (3,42 - 14,3)4,57 / 4,48
07247951EH1615DC1024x1418x35620,0 (8,00 - 20,0)16,8 (3,42 - 16,8)4,10 / 4,07

Notes

APPLICATION AT MEDIUM (LOW) TEMPERATURE ACCORDING THE REGULATIONS EU N° 811-813/2013
Seasonal space heating energy efficiency class:
A+ (A++) (mod. EH 0615 - 1015 DC)
A++ (A++) (mod. EH 1315 - 1615 DC)

Sound power:
60 dB(A) (mod. EH 0615 DC)
62 dB(A) (mod. EH 1015 - 1615 DC)


Refrigerant R410A (GWP=2088). Power supply: 230V~ 50Hz.
Data referred to the application with radiant panels and to the following conditions:
(*) Air: 7(6) °C - Water: 30/35 °C (Ref. A7 W35)
(**) Air: 35 °C - Water: 18/23 °C (Ref. A35 W18)
Perfomances according to EN 14511:2013